TG-5

$4,550.00
In stock
SKU
TG-5
Wilkins: Five Valve Backflow Prevention Assembly Test Gauge
Wilkins: 5 Valve Backflow Preventer Test Kit

ApplicationThe ZURN WILKINS Model TG-5 Backflow Prevention Assembly Test Kit is designed for testing all brands of Pressure Type Vacuum Breakers, Double Check Valve, and Reduced Pressure Principle Backflow Prevention Assemblies. The TG-5 is capable of performing all known testing procedures including those recommended by ASSE, AWWA and FCCCHR at USC.

MaterialsCase material:  Molded Plastic
Gauge body:  Thermoplastic
Fittings:  Brass (NPT & SAE)
Internals EP Elastomers, 316 Stainless Steel, Brass
Hose:  Buna Nitrile liner and jacket

CalibrationThe ZURN WILKINS Model TG-5 Backflow Prevention Assembly Test Kit is subjected to calibration testing conforming to standards traceable to the National Bureau of Standards. It is recommended that gauges be rechecked for calibration annually. ZURN WILKINS is not liable for shifts in calibration other than caused by defects.

FeaturesMaximum working pressure:  200 psi
Working temperature range 35° F to 150° F
Gauge body of engineered thermoplastic material
Gauge dial: 4 1/2” diameter, 0-15 P.S.I. scale (75 divisions)
200 psi line pressure gauge dial c Accuracy: +/- 0.2 P.S.I.D. (descending)
Valves: soft-seated needle with replaceable seats (5 total)
Hoses & end fittings: (3) color coded 5' lengths and (1) 4’ long clear bleed tube, SAE 45° flare fittings and 90 micron cleanable porous metal (brass) filters
5 year warranty against defects in materials and manufacturing
Durable carrying case with external fitting compart- ments
More Information
Model TG-5
Manufacturer Wilkins
Allow Overnight Shipping No
File Icon TG-5 Data Sheet (336.93 kB)